VCB Interrupter (vacuum circuit breaker arc extinguishing chamber) is a key component for efficient breaking and closing of current in power systems. It uses a high vacuum environment to ensure that the arc is quickly extinguished when the contacts are separated, and has excellent breaking performance and high reliability. The product has excellent insulation performance, environmental protection characteristics and long service life, and is widely used in medium and high voltage power transmission and distribution systems, such as industrial power grids, substations and rail transit, to ensure the safe operation of power equipment.
Features And Advantages Of Vcb Interrupter
1. High breaking capacity: vacuum medium quickly extinguishes arcs and adapts to high fault current environments.
2. Excellent insulation performance: vacuum environment provides extremely high dielectric strength to ensure system safety.
3. Environmentally friendly design: no harmful gas emissions, in line with green energy requirements.
4. Low maintenance cost: few mechanical parts, low wear and long service life.
5. Wide applicability: suitable for medium and high voltage power transmission and distribution scenarios, meeting various needs such as industry and substations.
Vcb Interrupter Precautions
1. Installation environment: ensure dryness, cleanliness, and no strong vibration and corrosive gas.
2. Operation specifications: follow the product manual to avoid overload or frequent switching.
3. Regular maintenance: check the vacuum degree, contact wear and mechanical component status to ensure stable performance.
4. Storage conditions: avoid high temperature, high humidity and strong magnetic field environment to prevent performance degradation.
5. Safety protection: insulation and protection measures must be taken during operation to ensure personnel safety.
Technical Parameters
| MAIN TECHNICAL DATA | ||
| Data | Unit | Value |
| Rated Frequency | Hz | 50 |
| Rated Voltage | kV | 12 |
| Rated Short-duration Withstand Voltage(1min) | kV | 48 |
| Rated Lightning Impulse Withstand Voltage | kV | 85 |
| Rated Current | A | 1600 |
| Circuit Resistance at the Lowest Rated Contact Force | μΩ | ≤20 |
| Rated Short-circuit Breaking Current | kA | 31.5 |
| Rated Short-circuit Breaking Current Breaking Times | Times | 50 |
| Rated Short-duration Withstand Current | kA | 31.5 |
| Rated Duration of Short-circuit | s | 4 |
| Rated Peak Withstand Current | kA | 80 |
| Rated Short-circuit Making Current | kA | 80 |
| Rated Operaing Sequence | O-0.3(0.5)s-CO-180s-CO | |
| Contact Stroke | mm | 11±1 |
| Contact Closing Force | N | 110±50 |
| Force Required to hold contacts open at full stroke | N | 180±50 |
| Average Opening Speed (first 75% stroke) | m/s | 1.4±0.2 |
| Average Closing Speed (last 30% stroke) | m/s | 0.8±0.2 |
| Rated Contact Force | N | 3100±200 |
| Contact Force at the Touch Point | N | 2200±150 |
| Contact Closing Bouncing Duration | ms | ≤2 |
| Contact Opening and Closing Non-simultaneity | ms | ≤2 |
| Contact Opening Rebound Amplitude | mm | ≤2 |
| Storage Life | Years | 20 |
| Mechanical Endurance | Times | 10000 |
| Contact Erosion Limit | mm | 3 |
Hot Tags: vcb interrupter, China vcb interrupter manufacturers, suppliers, factory, vacuum interrupter for hospital facilities, vacuum interrupter for defense applications, vacuum interrupter for government buildings, vacuum interrupter for renewable energy systems, vacuum interrupter for wastewater treatment systems, vacuum interrupter for otolaryngological equipment