Vacuum Interrupter utilizes vacuum arc extinguishing technology to provide efficient current interruption for high voltage power systems. It utilizes the high insulating properties of the vacuum medium to ensure rapid arc extinguishing under fault current conditions, protecting equipment and the power grid. With long service life, low maintenance requirements and high reliability, the product adapts to various harsh environments and is widely used in substations, industrial power grids and wind power generation. Their environmentally friendly characteristics make them compliant with modern green energy standards, making them an efficient, safe and durable power solution.
Vacuum Interrupter usually does not require frequent maintenance. Due to the vacuum medium, there is almost no wear when the arc is extinguished, the contact life is long, and there is no oil or gas medium that needs to be replaced regularly. It has high durability and can withstand a large number of interruption operations without degradation.
But regular inspection and cleaning are required to ensure the normal operation of the equipment in extreme environments. For example, in a high humidity and high pollution environment, it is necessary to check the exterior and insulation of the equipment to prevent dust or corrosion from affecting its performance.
Precautions
1. Installation environment: Ensure that the equipment is installed in a dry, clean environment to avoid pollutants and moisture from entering the interior of the equipment.
2. Regular inspection: Although the maintenance needs are low, it is still necessary to regularly check the equipment shell, contacts and sealing components to ensure that there is no damage or leakage.
3. Avoid overload operation: Avoid overloading the equipment, follow the rated parameters, and prevent frequent overload switching operations.
4. Prevent external impact: Avoid strong external impact or vibration on the equipment to avoid damage to the vacuum vessel.
5. Avoid strong corrosive environment: when used in extreme corrosive environment, the shell and sealing device should be checked regularly to prevent corrosion from affecting the performance of the equipment.
6. Operation standardization: operate the equipment according to the instruction manual to ensure its efficient and safe operation.



Technical Parameters
| MAIN TECHNICAL DATA | ||
| Data | Unit | Value |
| Rated Frequency | Hz | 50/60 |
| Rated Voltage | kV | 12 |
| Rated Short-duration Withstand Voltage(1min) | kV | 48 |
| Rated Lightning Impulse Withstand Voltage | kV | 85 |
| Rated Current | A | 4000 |
| Circuit Resistance at the Lowest Rated Contact Force | μΩ | ≤25 |
| Rated Short-circuit Breaking Current | kA | 25 |
| Rated Short-circuit Breaking Current Breaking Times | Times | 30 |
| Rated Short-duration Withstand Current | kA | 50 |
| Rated Duration of Short-circuit | s | 4 |
| Rated Peak Withstand Current | kA | 125 |
| Rated Short-circuit Making Current | kA | 125 |
| Rated Operaing Sequence | open-180s-co-180s-co | |
| Contact Stroke | mm | 9±1 |
| Contact Closing Force | N | 210±50 |
| Force Required to hold contacts open at full stroke | N | 280±50 |
| Average Opening Speed (first 75% stroke) | m/s | 1.2±0.2 |
| Average Closing Speed (last 30% stroke) | m/s | 0.6±0.2 |
| Rated Contact Force | N | 6750±750 |
| Contact Force at the Touch Point | N | 4750±750 |
| Contact Closing Bouncing Duration | ms | ≤2 |
| Contact Opening and Closing Non-simultaneity | ms | ≤2 |
| Contact Opening Rebound Amplitude | mm | ≤2 |
| Storage Life | Years | 20 |
| Mechanical Endurance | Times | 10000 |
| Contact Erosion Limit | mm | 3 |
| Overtravel during Opening | mm | ≤2 |
Hot Tags: vacuum interrupter price, China vacuum interrupter price manufacturers, suppliers, factory, vacuum interrupter for hoists, vacuum interrupter for swimming pools, vacuum interrupter for primary circuit, vacuum interrupter for electric traction, vacuum interrupter for universities, vacuum interrupter for automation circuit protection