11KV Vacuum Interrupter is a vacuum interrupter for 11 kilovolt (KV) power systems. It uses vacuum media to quickly extinguish arcs, thereby effectively interrupting current and protecting electrical equipment and power systems from damage caused by faults such as overload or short circuit.
Mainly Used In The Following Areas
1. Distribution system: used for switch protection of medium and high voltage distribution lines to ensure the stability and safety of power transmission.
2. Substation: used in substations to protect and isolate circuits, prevent faults from spreading, and ensure the safety of equipment and personnel.
3. Industrial power system: widely used in power control systems of industrial enterprises to protect electrical equipment from overload or short circuit.
4. Power facility protection: used for fault detection and isolation of power lines to improve the stability of power facilities.
5. Power plant: used in the power distribution and protection system of the power plant to ensure power stability during power generation.
6. Renewable energy system: used in wind and solar power generation systems to ensure the electrical safety and stable operation of the system.









Technical Parameters
| MAIN TECHNICAL DATA | ||
| Data | Unit | Value |
| Rated Frequency | Hz | 50 |
| Rated Voltage | kV | 12 |
| Rated Short-duration Withstand Voltage(1min) | kV | 48/28in air |
| Rated Lightning Impulse Withstand Voltage | kV | 85/60in air |
| Rated Current | A | 1250 |
| Circuit Resistance at the Lowest Rated Contact Force | μΩ | ≤15 |
| Rated Short-circuit Breaking Current | kA | 25 |
| Rated Short-circuit Breaking Current Breaking Times | Times | 50 |
| Rated Short-duration Withstand Current | kA | 25 |
| Rated Duration of Short-circuit | s | 4 |
| Rated Peak Withstand Current | kA | 63 |
| Rated Short-circuit Making Current | kA | 63 |
| Rated Operaing Sequence | O-0.3(0.5)s-CO-180s-CO | |
| Contact Stroke | mm | 9±1 |
| Contact Closing Force | N | 100±30 |
| Force Required to hold contacts open at full stroke | N | 150±40 |
| Average Opening Speed (first 75% stroke) | m/s | 1.0±0.2 |
| Average Closing Speed (last 30% stroke) | m/s | 0.6±0.2 |
| Rated Contact Force | N | 2000±200 |
| Contact Force at the Touch Point | N | 1400±150 |
| Contact Closing Bouncing Duration | ms | ≤2 |
| Contact Opening and Closing Non-simultaneity | ms | ≤2 |
| Contact Opening Rebound Amplitude | mm | ≤2 |
| Storage Life | Years | 20 |
| Mechanical Endurance | Times | 10000 |
| Contact Erosion Limit | mm | 3 |
Hot Tags: 11kv vacuum interrupter, China 11kv vacuum interrupter manufacturers, suppliers, factory, vacuum interrupter for signal circuit protection, vacuum interrupter for secondary circuit protection, reliable vacuum interrupter, vacuum interrupter for gymnasiums, vacuum interrupter for automotive industry, vacuum interrupter for supply chain management