BHA/VNA Load Switch/disconnector

BHA/VNA Load Switch/disconnector

1.General Description: The BHA series Load Break Switch, incorporating proven flat-chamber arcing technology, can perform a wide variety of switching functions in medium voltage distribution systems. They are the result of more than 40 year's experience in development and manufacture of load...
Send Inquiry
Description

1. General Description

The BHA series Load Break Switch, incorporating proven flat-chamber arcing technology, can perform a wide variety of switching functions in medium-voltage distribution systems. They are the result of more than 50 year's experience in development and manufacture of load break switch by SHONEVAC. The simple, low-maintenance and highly economic indoor load break switch in the BHA series have a proven service record, with hundreds of thousands of units installed and operating on a wide range of systems.

 

The BHA load break switch comply with the requirements of IEC 60694 (EN 60694) and IEC 60265-1 (EN 60265-1). Additionally, selected variants are available, complying with IEC 62271-105 (EN 62271-105).

 

2. Main applications

BHA series load break switc is designed for use in indoor medium- voltage switchgear systems. They have a making capacity and are suitable for switching:

  • load currents
  • currents in ring mains
  • transformers, cables and overhead lines.

BHA load break switch is the reliable and economic solution for refurbishment and maintenance programs, extensions, renewal or upgrading of personnel protection.

 

3. Special features

  • high reliability and long service life
  • low operating cost due to long periods between maintenance procedures
  • space-saving design
  • high switching capability
  • low operating torques
  • suitable for use in in harsh climatic conditions
  • ideal as substitute for older load break switch
  • load break switch-fuse combination to IEC 62271-105 (EN 62271-105) available.

 

 

4. Technical Data

 

Rated voltage Un KV 12KV
Rated current In A 630 1250
Max. rated current I A 630 1150
Short circuit making capacity Ima KA peak 63 63
Peak withstand current Idyn KA peak 63 63

Short time current         1 sec.

                                      2 sec.

                                      3 sec.

Ith KA eff 25 25
Ith KA eff 20 20
Ith KA eff 18 18
Mainly active load breaking capacity (test duty 1 and 2, IEC 265) I A 630 1250
Mainly capacitive breaking capacity (test duty 4, IEC 265) I A 150 150
Max. breaking capacity in co-operation with fuses (IEC 420 1990-11) A   1600
Max. fuse size In A 125

Power frequency withstand voltage 50Hz 1min - to earth and between poles

                                                                           - across isolating distance

  KV 42
48
  KV

Impulse withstand voltage 1,2/50 us. - to earth and between poles

                                                           - across isolating distance

  KV 75
85
  KV
Pole distance P mm 150,170,210

 

 

5. Applicable environment

The switch is used for three-line AC 50Hz circuit, for the use of voltage and no load when the circuit.The basic conditions of use are as follows :

  • Ambient temperature:-25C~+40°C;
  • Altitude: ≤1000m;
  • Relative humidity: daily average ≤95%, monthly average ≤90%;
  • Earthquake intensity:≤8 level;
  • Installation places: no fire, explosion hazard,serious filthy,chemical corrosion or severe vibration.

 

6. Dimension

 

 

 

53413790-9931-4545-a86f-833322992870

 

BHA-12D; 12kV/630A

3872ee13-4f8e-4da1-b036-14bb4176c26e
BHA-12RD; 12kV/630A

 

7 TRANSPORTATION AND STORAGE

Transportation of switch should be carried out by any type of transport in accordance with the Rules for the Transportation of Goods in force for each type of transport. Transportation of packaged disconnectors should exclude the possibility of direct exposure to atmospheric precipitation and aggressive environments.

 

8 DISPOSAL

Switches are made of metal and porcelain and do not contain substances that can harm health and the environment. Switches after the end of their service life are subject to transfer to organizations that process ferrous and non-ferrous metals. If the packaging is no longer needed, it can be completely recycled.

 

9 MANUFACTURER'S WARRANTIES

The manufacturer's warranty is void if one of the following occurs:

– non-original parts not manufactured by the company are used;

– the personnel performing the replacement have not been trained in accordance with the Electrical Installation Code;

– parts are not mounted or adjusted correctly;

– the adjustment is carried out in violation of the instructions in the Operating Manual.

 

The warranty period is 1 years from the date of sale, subject to compliance with the operating and storage conditions, but not more than 5 years from the date of manufacture. The guaranteed shelf life for the consumer in the manufacturer's packaging is 1 years. The service life is no more than 25 years from the date of manufacture.

 

 
Please  Contact with us to get the Catalogue documents.
 
 

Hot Tags: bha/vna load switch/disconnector, China bha/vna load switch/disconnector manufacturers, suppliers, factory

Send Inquiry

Send Inquiry