1. General Description
The BHA series Load Break Switch, incorporating proven flat-chamber arcing technology, can perform a wide variety of switching functions in medium-voltage distribution systems. They are the result of more than 50 year's experience in development and manufacture of load break switch by SHONEVAC. The simple, low-maintenance and highly economic indoor load break switch in the BHA series have a proven service record, with hundreds of thousands of units installed and operating on a wide range of systems.
The BHA load break switch comply with the requirements of IEC 60694 (EN 60694) and IEC 60265-1 (EN 60265-1). Additionally, selected variants are available, complying with IEC 62271-105 (EN 62271-105).
2. Main applications
BHA series load break switc is designed for use in indoor medium- voltage switchgear systems. They have a making capacity and are suitable for switching:
- load currents
- currents in ring mains
- transformers, cables and overhead lines.
BHA load break switch is the reliable and economic solution for refurbishment and maintenance programs, extensions, renewal or upgrading of personnel protection.
3. Special features
- high reliability and long service life
- low operating cost due to long periods between maintenance procedures
- space-saving design
- high switching capability
- low operating torques
- suitable for use in in harsh climatic conditions
- ideal as substitute for older load break switch
- load break switch-fuse combination to IEC 62271-105 (EN 62271-105) available.
4. Technical Data
| Rated voltage | Un | KV | 12KV | |
| Rated current | In | A | 630 | 1250 |
| Max. rated current | I | A | 630 | 1150 |
| Short circuit making capacity | Ima | KA peak | 63 | 63 |
| Peak withstand current | Idyn | KA peak | 63 | 63 |
|
Short time current 1 sec. 2 sec. 3 sec. |
Ith | KA eff | 25 | 25 |
| Ith | KA eff | 20 | 20 | |
| Ith | KA eff | 18 | 18 | |
| Mainly active load breaking capacity (test duty 1 and 2, IEC 265) | I | A | 630 | 1250 |
| Mainly capacitive breaking capacity (test duty 4, IEC 265) | I | A | 150 | 150 |
| Max. breaking capacity in co-operation with fuses (IEC 420 1990-11) | A | 1600 | ||
| Max. fuse size | In | A | 125 | |
|
Power frequency withstand voltage 50Hz 1min - to earth and between poles - across isolating distance |
KV | 42 48 |
||
| KV | ||||
|
Impulse withstand voltage 1,2/50 us. - to earth and between poles - across isolating distance |
KV | 75 85 |
||
| KV | ||||
| Pole distance | P | mm | 150,170,210 | |
5. Applicable environment
The switch is used for three-line AC 50Hz circuit, for the use of voltage and no load when the circuit.The basic conditions of use are as follows :
- Ambient temperature:-25C~+40°C;
- Altitude: ≤1000m;
- Relative humidity: daily average ≤95%, monthly average ≤90%;
- Earthquake intensity:≤8 level;
- Installation places: no fire, explosion hazard,serious filthy,chemical corrosion or severe vibration.
6. Dimension

BHA-12D; 12kV/630A

7 TRANSPORTATION AND STORAGE
Transportation of switch should be carried out by any type of transport in accordance with the Rules for the Transportation of Goods in force for each type of transport. Transportation of packaged disconnectors should exclude the possibility of direct exposure to atmospheric precipitation and aggressive environments.
8 DISPOSAL
Switches are made of metal and porcelain and do not contain substances that can harm health and the environment. Switches after the end of their service life are subject to transfer to organizations that process ferrous and non-ferrous metals. If the packaging is no longer needed, it can be completely recycled.
9 MANUFACTURER'S WARRANTIES
The manufacturer's warranty is void if one of the following occurs:
– non-original parts not manufactured by the company are used;
– the personnel performing the replacement have not been trained in accordance with the Electrical Installation Code;
– parts are not mounted or adjusted correctly;
– the adjustment is carried out in violation of the instructions in the Operating Manual.
The warranty period is 1 years from the date of sale, subject to compliance with the operating and storage conditions, but not more than 5 years from the date of manufacture. The guaranteed shelf life for the consumer in the manufacturer's packaging is 1 years. The service life is no more than 25 years from the date of manufacture.
Hot Tags: bha/vna load switch/disconnector, China bha/vna load switch/disconnector manufacturers, suppliers, factory