A vacuum interrupter is a switch that uses vacuum electrical contacts in electrical engineering. It is a core component of medium voltage circuit breakers, generator circuit breakers, and high voltage circuit breakers. Vacuum interrupters are mainly used in circuit breakers and load switches. Among them, vacuum interrupters used in circuit breakers are mainly used in power departments such as substations and power grid facilities. Compared with high voltage vacuum circuit breakers, low voltage vacuum circuit breakers have the advantages of small size, light weight, compact structure, long life, and low maintenance cost. It is mainly used to control and protect low voltage circuits. It can quickly cut off the current when a circuit fault occurs to prevent the fault from expanding and damaging the equipment.
Precautions for use
1. Rated value limitation:
When using vacuum circuit breakers, make sure that the working voltage and working current do not exceed the rated value of vacuum circuit breakers to avoid overloading or damaging the equipment.
2. Breaking capacity:
Vacuum circuit breaker has a certain breaking capacity, should be based on the actual need to choose the appropriate breaking capacity of the vacuum circuit breaker, to ensure that in the event of circuit failure can quickly cut off the current.
3. Cooperation with other equipment:
Vacuum circuit breakers may need to be used in conjunction with other electrical equipment such as fuses and disconnect switches. When selecting vacuum circuit breakers, you need to consider the compatibility and cooperation with other equipment.

Technical Parameters
| MAIN TECHNICAL DATA | ||
| Data | Unit | Value |
| Rated Frequency | Hz | 50/60 |
| Rated Voltage | kV | 12 |
| Rated Short-duration Withstand Voltage(1min) | kV | 48 |
| Rated Lightning Impulse Withstand Voltage | kV | 85 |
| Rated Current | A | 2000 |
| Rated Short-duration Withstand Current | kA | 31.5 |
| Rated Duration of Short-circuit | s | 4 |
| Rated Peak Withstand Current | kA | 80 |
| Rated Short-circuit Making Current | kA | 80 |
| Rated Short-circuit Breaking Current | kA | 31.5 |
| Max. DC component | 50% | |
| Rated Short-circuit Breaking Current Breaking Times | Times | 30 |
| Rated Single Capacitor Bank Breaking Current | A | 630 |
| Rated Back-to-back Capacitor Bank Breaking Current | A | 400 |
| Mechanical Endurance | Times | 10000 |
| Contact Stroke | mm | 11±1 |
| Contact Closing Force | N | 110±40 |
| Force Required to hold contacts open at full stroke | N | 190±40 |
| Circuit Resistance at the Lowest Rated Contact Force | μΩ | ≤20 |
| Contact Erosion Limit | mm | 3 |
| Mass of Moving Parts | kg | 2.8 |
| Internal Gas Pressure | Pa | ≤1.33x10-3 |
| Rated Operaing Sequence | O-180s-CO-180s-CO | |
| Storage Life | Years | 20 |
| Average Opening Speed (first 75% stroke) | m/s | 1.2±0.2 |
| Average Closing Speed (last 30% stroke) | m/s | 0.6±0.2 |
| Contact Closing Bouncing Duration | ms | ≤2 |
| Contact Opening and Closing Non-simultaneity | ms | ≤1 |
| Rated Contact Force | N | 3200+500 |
| Contact Force at the Touch Point | N | 2300+350 |
| Contact Opening Rebound Amplitude | mm | ≤2 |
Hot Tags: vacuum interrupter for low vcb, China vacuum interrupter for low vcb manufacturers, suppliers, factory, vacuum interrupter for augmented reality systems, vacuum interrupter for protection circuit, vacuum interrupter for ophthalmological equipment, vacuum interrupter for alarm circuit protection, vacuum interrupter for repair protection, vacuum interrupter for upgrade protection