High Voltage Interrupter is a current interruption device used in high voltage power systems. It can quickly cut off the current when a current fault occurs to protect power equipment from damage. It usually uses a vacuum medium to extinguish the arc to ensure the safety and stability of the circuit.
The Main Components Are As Follows
1. Arc extinguishing chamber: provides efficient arc extinguishing capability, can quickly cut off the current, and reduce the damage of arc to the equipment.
2. Contact: adopts high temperature resistant and wear-resistant materials to extend the service life and reduce the need for maintenance.
3. Insulator: has excellent electrical insulation performance to ensure the safety and stability of the equipment.
4. Sealing device: ensures the sealing of the internal environment, prevents the entry of external pollutants, and maintains good working condition.
5. Drive device: provides precise and fast contact operation to ensure efficient current interruption.
6. Shell: provides physical protection, resists external impact, corrosion and harsh environmental influences, and increases the durability of the equipment.



Technical Parameters
| MAIN TECHNICAL DATA | ||
| Data | Unit | Value |
| Rated Frequency | Hz | 50 |
| Rated Voltage | kV | 12 |
| Rated Short-duration Withstand Voltage(1min) | kV | 48 |
| Rated Lightning Impulse Withstand Voltage | kV | 85 |
| Rated Current | A | 4000 |
| Circuit Resistance at the Lowest Rated Contact Force | μΩ | ≤10 |
| Rated Short-circuit Breaking Current | kA | 50 |
| Rated Short-circuit Breaking Current Breaking Times | Times | 30 |
| Rated Short-duration Withstand Current | kA | 50 |
| Rated Duration of Short-circuit | s | 4 |
| Rated Peak Withstand Current | kA | 125 |
| Rated Short-circuit Making Current | kA | 125 |
| Rated Operaing Sequence | open-180s-co-180-co | |
| Contact Stroke | mm | 9±1 |
| Contact Closing Force | N | 210±50 |
| Force Required to hold contacts open at full stroke | N | 280±50 |
| Average Opening Speed (first 75% stroke) | m/s | 1.2±0.2 |
| Average Closing Speed (last 30% stroke) | m/s | 0.6±0.2 |
| Rated Contact Force | N | 6750+750 |
| Contact Force at the Touch Point | N | 4750+500 |
| Contact Closing Bouncing Duration | ms | ≤2 |
| Contact Opening and Closing Non-simultaneity | ms | ≤2 |
| Storage Life | Years | 20 |
| Contact Erosion Limit | mm | 3 |
Hot Tags: high voltage interrupter, China high voltage interrupter manufacturers, suppliers, factory, vacuum interrupter for hoists, vacuum interrupter for integrated circuits, vacuum interrupter for air conditioning systems, vacuum interrupter for project protection, vacuum interrupter for petrochemical industry, vacuum interrupter with flexible configuration