High Voltage Vacuum Interrupter

High voltage vacuum interrupter, also called vacuum switching tube, is the core component of medium and high voltage power switch. Its role is to allow medium and high voltage circuits to cut off the power supply can quickly extinguish the arc and inhibit the current, to protect the safe operation of equipment and systems. It is widely used in power transmission and distribution control system, as well as metallurgy, mining, petroleum, chemical industry, railroad, broadcasting, communication, industrial high-frequency heating and other power distribution systems.
Send Inquiry
Description

High voltage vacuum interrupter, also called vacuum switching tube, is the core component of medium and high voltage power switch. Its role is to allow medium and high voltage circuits to cut off the power supply can quickly extinguish the arc and inhibit the current, to protect the safe operation of equipment and systems. It is widely used in power transmission and distribution control system, as well as metallurgy, mining, petroleum, chemical industry, railroad, broadcasting, communication, industrial high-frequency heating and other power distribution systems.

 

Features

 

1. Rapid arc quenching and current suppression:

High-voltage vacuum arc extinguishing chamber through the tube vacuum excellent insulation, so that the medium and high voltage circuit cut off the power supply can quickly quench the arc and inhibit the current, effectively prevent accidents and accidents.

2. Energy saving and environmental protection:

The arc extinguishing chamber is characterized by energy-saving, material-saving, fireproof, explosion-proof, and small size, long service life, low maintenance costs, reliable operation and no pollution.

3. Structural stability:

There is a shielding system inside the high voltage vacuum interrupter room, which is mainly composed of shielding cylinder, shielding cover and other parts. Can prevent the contacts in the combustion arc process to produce a large number of metal vapors and droplets splashing, to avoid contamination of the inner wall of the insulation shell, to prevent the cause of the vacuum interrupter room shell insulation strength decline or flashover. At the same time, the shielding system can also improve the electric field distribution inside the vacuum interrupter, which is conducive to the miniaturization of the insulation shell of the vacuum interrupter, especially for the miniaturization of high-voltage vacuum interrupter has a significant effect.

4. Efficient heat dissipation:

The metal shielding cylinder inside the arc extinguishing chamber can not only play a safe isolation and limit the role of arc diffusion, but also be able to direct the arc to the fuse, so that the arc is extinguished inside the fuse. And the metal shielding cylinder can also help dissipate heat, avoid overheating leading to equipment damage or reduce work efficiency.

5. Opening and closing capacity:

The contact is the part that generates arcs and extinguishes arcs, and has high requirements for materials and structure. High-voltage vacuum interrupter adopts high-performance contact materials and structure, with high breaking capacity, can quickly cut off the fault current, to protect the safe operation of the power system.

6. Long mechanical life:

Vacuum interrupter bellows is made of stainless steel thickness of 0.1 ~ 0.2mm thin-walled components, mainly responsible for ensuring that the dynamic electrode in a certain range of movement and long-term maintenance of high vacuum function, therefore, the service life of high-voltage vacuum interrupter are generally very long.

 

P101

P103

P104

Technical Parameters

 

Data Unit Value
Rated Frequency Hz 50
Rated Voltage kV 12
Rated Short-duration Withstand Voltage(1min) kV 48
Rated Lightning Impulse Withstand Voltage kV 85
Rated Current A 630
Circuit Resistance at the Lowest Rated Contact Force μΩ ≤35
Rated Short-circuit Breaking Current kA 25
Rated Short-circuit Breaking Current Breaking Times Times 30
Rated Short-duration Withstand Current kA 25
Rated Duration of Short-circuit s 4
Rated Peak Withstand Current kA 63
Rated Short-circuit Making Current kA 63
Rated Operaing Sequence   O-0.3(0.5)s-CO-180s-CO
Contact Stroke mm 9±1
Contact Closing Force N 60±30
Force Required to hold contacts open at full stroke N 140±30
Average Opening Speed (first 75% stroke) m/s 1.2±0.2
Average Closing Speed (last 30% stroke) m/s 0.6±0.2
Rated Contact Force N 2000±200
Contact Force at the Touch Point N 1400±100
Contact Closing Bouncing Duration ms ≤2
Contact Opening and Closing Non-simultaneity ms ≤1
Contact Opening Rebound Amplitude mm ≤2
Storage Life Years 20
Mechanical Endurance Times 10000
Contact Erosion Limit mm 3

 

Hot Tags: high voltage vacuum interrupter, China high voltage vacuum interrupter manufacturers, suppliers, factory, vacuum interrupter for power generation, innovative vacuum interrupter, vacuum interrupter for fishing equipment, vacuum interrupter for office buildings, vacuum interrupter for power factor correction, vacuum interrupter for supply chain management

Send Inquiry

Send Inquiry