Medium Voltage Vacuum Interrupter

Vacuum interrupter is the core component of the circuit breaker, which is composed of ceramic cylindrical tube section, metal cover and internal contacts.Medium-voltage vacuum circuit breaker is a kind of circuit breaker that utilizes vacuum as the arc extinguishing medium, and its main function is to switch, fault protection and isolation of circuits in the power system. When there is a short circuit or overload and other abnormalities in the circuit, the vacuum circuit breaker can quickly cut off the circuit to protect the safe and stable operation of the power system.
Send Inquiry
Description

Vacuum interrupter is the core component of the circuit breaker, which is composed of ceramic cylindrical tube section, metal cover and internal contacts.Medium-voltage vacuum circuit breaker is a kind of circuit breaker that utilizes vacuum as the arc extinguishing medium, and its main function is to switch, fault protection and isolation of circuits in the power system. When there is a short circuit or overload and other abnormalities in the circuit, the vacuum circuit breaker can quickly cut off the circuit to protect the safe and stable operation of the power system. Medium-voltage vacuum circuit breaker usually consists of vacuum interrupter, operating mechanism, transmission parts, insulation parts and shell and so on.

 

Working Principle

 

When the operating mechanism receives the opening or closing signal, it will drive the transmission components to make the internal contacts open and close. During the opening process, the contacts separate quickly and generate an arc. Due to the high vacuum in the vacuum interrupter, the arc is quickly extinguished, thereby cutting off the circuit. During the closing process, the contacts are in close contact, forming a conductive path, so that the circuit can be closed.

 

Application Areas

 

Medium voltage vacuum circuit breakers are widely used in various medium voltage switchgear in power systems, such as substations, power plants, distribution stations, etc. They are not only used for circuit switching and protection, but also for automatic control and remote monitoring of power systems.

 

C-UserslzyDesktop107BP101

C-UserslzyDesktop107BP103

C-UserslzyDesktop107BP106

Technical Parameters

 

MAIN TECHNICAL DATA    
Data Unit Value
Rated Frequency Hz 50
Rated Voltage kV 12
Rated Short-duration Withstand Voltage kV 48/28(in air)
Rated Lightning Impulse Withstand Voltage kV 85/60(in air)
Rated Current A 630
Circuit Resistance at the Lowest Rated Contact Force μΩ ≤25
Rated Short-circuit Breaking Current kA 20
Rated Short-circuit Breaking Current Breaking Times Times 50
Rated Short-duration Withstand Current kA 20
Rated Duration of Short-circuit s 4
Rated Peak Withstand Current kA 50
Rated Short-circuit Making Current kA 50
Rated Operaing Sequence   O-0.3(0.5)s-CO-180s-CO
Contact Stroke mm 9±1
Contact Closing Force N 80±25
Force Required to hold contacts open at full stroke N 150±40
Average Opening Speed (first 75% stroke) m/s 1.1±0.3
Average Closing Speed (last 30% stroke) m/s 0.7±0.2
Rated Contact Force N 2000±200
Contact Force at the Touch Point N 1400±100
Contact Closing Bouncing Duration ms ≤2
Contact Opening and Closing Non-simultaneity ms ≤2
Contact Opening Rebound Amplitude mm ≤2
Storage Life Years 20
Mechanical Endurance Times 10000
Contact Erosion Limit mm 3

 

Hot Tags: medium voltage vacuum interrupter, China medium voltage vacuum interrupter manufacturers, suppliers, factory, vacuum interrupter for medical devices, vacuum interrupter for townhouses, vacuum interrupter for home appliances, vacuum interrupter for healthcare equipment, vacuum interrupter for protection circuit protection, vacuum interrupter for converters