Molded Vacuum Interrupter is an interruption device that uses vacuum arc extinguishing technology and is commonly used in high-voltage power systems. Unlike traditional vacuum interrupters, the main feature of Molded Vacuum Interrupter is that its shell is injection molded with plastic or composite materials, which is more compact and lightweight. Vacuum medium is used inside to quickly extinguish the arc to prevent damage to the power system and equipment.
The advantages of this interrupter design include smaller size, stronger high-voltage resistance, low maintenance requirements and good electrical insulation performance. It is widely used in various distribution systems, substations and other power facilities that require rapid current interruption.
The Benefits Of Molded Vacuum Interrupter Include
1. Efficient current interruption: quickly extinguish arcs and protect power equipment.
2. Strong reliability: long-term stable operation and reduced failures.
3. Save maintenance costs: low maintenance requirements, reduced maintenance work and expenses.
4. Environmental protection: no oil and harmful gas emissions, in line with green environmental protection requirements.
5. Strong adaptability: able to work normally in harsh environments.



Technical Parameters
| MAIN TECHNICAL DATA | ||
| Data | Unit | Value |
| Rated Frequency | Hz | 50 |
| Rated Voltage | kV | 12 |
| Rated Short-duration Withstand Voltage(1min) | kV | 48/28in air |
| Rated Lightning Impulse Withstand Voltage | kV | 85/60 in air |
| Rated Current | A | 1600 |
| Circuit Resistance at the Lowest Rated Contact Force | μΩ | ≤20 |
| Rated Short-circuit Breaking Current | kA | 31.5 |
| Rated Short-circuit Breaking Current Breaking Times | Times | 50 |
| Rated Short-duration Withstand Current | kA | 31.5 |
| Rated Duration of Short-circuit | s | 4 |
| Rated Peak Withstand Current | kA | 80 |
| Rated Short-circuit Making Current | kA | 80 |
| Rated Operaing Sequence | O-0.3(0.5)s-CO-180s-CO | |
| Contact Stroke | mm | 11±1 |
| Contact Closing Force | N | 140±50 |
| Force Required to hold contacts open at full stroke | N | 220±50 |
| Average Opening Speed (first 75% stroke) | m/s | 1.1±0.2 |
| Average Closing Speed (last 30% stroke) | m/s | 0.6±0.2 |
| Rated Contact Force | N | 3100±200 |
| Contact Force at the Touch Point | N | 2200±150 |
| Contact Closing Bouncing Duration | ms | ≤2 |
| Contact Opening and Closing Non-simultaneity | ms | ≤2 |
| Contact Opening Rebound Amplitude | mm | ≤2 |
| Storage Life | Years | 20 |
| Mechanical Endurance | Times | 10000 |
| Contact Erosion Limit | mm | 3 |
Hot Tags: molded vacuum interrupter, China molded vacuum interrupter manufacturers, suppliers, factory, vacuum interrupter with high breaking capacity, vacuum interrupter for thermal protection, Medium Voltage Vacuum Interrupter, indoor vacuum interrupter, vacuum interrupter for energy storage systems, vacuum interrupter for replacement protection