Opening Speed Of Vacuum Circuit Breaker

Dec 15, 2024 Leave a message

Generally speaking, the faster the opening speed of a circuit breaker, the better, so that the first phase can break the fault current 2-3ms before the current approaches zero; Otherwise, the first phase cannot be disconnected and continues to the next phase, causing the original first phase to change to a later phase, prolonging the arc time and increasing the difficulty of disconnection, even leading to disconnection failure. But if the opening speed is too fast, the rebound of the opening will also be large. If the rebound is too large and the vibration is too intense, it is easy to cause reignition. Therefore, the opening speed should also consider this factor. The speed of opening depends mainly on the energy storage capacity of the moving contact spring and the opening spring when closing. In order to improve the opening speed, the energy storage of the opening spring can be increased, and the compression of the closing spring can also be increased, which inevitably requires an increase in the output power of the operating mechanism and the mechanical strength of the whole machine, reducing the technical and economic indicators. After years of testing, it is believed that a 10kV vacuum circuit breaker with an average opening speed of 0.95-1.2m/s is more suitable.

 